| Type |
|
Finder 80.01.0.240.000 |
| Contact specification |
|
|
| Contact configuration |
|
1 CO (SPDT) |
| Rated current / Maximum peak current |
|
16 / 30 A |
| Rated switching voltage |
|
250 VAC |
| Maximum switching voltage |
|
400 VAC |
| Rated load AC1 |
|
4000 VA |
| Rated load AC15 (230 V AC) |
|
750 VA |
| Single-phase motor rating (230 V AC) |
|
0.55 KW |
| Breaking capacity DC1: 30/110/22 |
|
16 / 0.3 / 0.12 VA |
| Minimum switching load |
|
500 (10/5) mW (V/mA) |
| Standard contact material |
|
AgNi |
| Supply specification |
|
|
| Nominal voltage (UN) |
|
12 to 240 V AC (50/60 Hz) |
| |
|
12 to 240 VDC |
| Rated power AC/DC VA (50 Hz)/W |
|
< 1.8 / < 1 |
| Operating range |
|
10.8 to 265 VAC |
| |
|
10.8 to 265 VDC |
| Technical data |
|
|
| Specified time range |
|
(0.1 to 2)s, (1 to 20)s, (0.1 to 2)min |
| |
|
(1 to 20)min, (0.1 to 2)h, (1 to 24)h |
| Repeatability |
|
± 1% |
| Recovery time |
|
100 ms |
| Minimum control impulse |
|
50 ms |
| Setting full accuracy range |
|
± 5% |
| Electrical life at rated load in AC1 cycles |
|
50 x 103 |
| Ambient temperature range |
|
–20 to +60 °C |
| Protection category |
|
IP 20 |