Type |
|
R15-2012-23-1024-WT Relpol |
Contact configuration |
|
2 Change Over (DPDT) |
Rated current / Maximum peak current |
|
10 / 20A |
Rated voltage / Maximum switching voltage |
|
250 / 440VAC |
Rated load AC1 |
|
10A @ 250VAC |
Rated load AC15 |
|
3A @ 120VAC / 1.5A @ 240VAC |
Single-phase motor rating (240V AC) |
|
0.37kW |
Breaking capacity DC1 |
|
10A @ 24VDC |
Minimum switching load |
|
5mA |
Standard contact material |
|
AgNi |
Coil specification |
|
|
Nominal voltage |
|
24VDC |
Rated power |
|
1.5W |
Operating range |
|
19.2 to 26.4VDC |
Holding voltage |
|
12VDC |
Must drop-out voltage |
|
2.4VDC |
Technical data |
|
|
Mechanical life |
|
2 x 10^7 |
Electrical life at rated load AC1 (cycles) |
|
2 x 10^5 |
Operate / release time |
|
18 / 7ms |
Insulation between coil and contacts (1.2/50 μs) |
|
2.5kV |
Dielectric strength between open contacts |
|
1500VAC |
Ambient temperature range |
|
–40 to +70°C |
Environmental protection |
|
RT I |
Dimensions (L x H x W) |
|
35 x 54.4 x 35 mm |
Approvals |
|
UL, VDE, EAC, CE and CSA |
Suitable DIN relay base |
|
Finder 9022 |